Categories
Article No. 296.045.754
E-Number 808 408 000
Technical specification
SPD type T3  
Number of poles 4  
max. discharge current (Imax) 15  
Nominal line voltage Un AC 230  
Continuous voltage AC max. 275  
Nominal frequency [fn] 50.0 - 60.0 Hz
Discharge current max. (8/20) µs [Imax] 15  
Nominal discharge surge current (8/20) 5  
Combined shock [Uoc] 10  
Voltage protection level [Up] 0.9  
Operating current [Ic] 0  
Follow current [IF] 0  
follow current extinguishing capability [Ifi] Unendlich kA eff  
Response time [ta] 0 ns  
TOV-voltage L-N [UT] 335 V / 5 sec.  
TOV-voltage N-PE [UT] 1200 V / 300 A / 200ms fest  
Short circuit resistance (Icw) 10  
Fault indication Mechanisch, rot  
Temperature range -40.0 - 85.0 °C
Degree of protection IP20  
Fuse max. (gG) 40  
Mounting on Hutschiene 35 mm  
Material housing  
Signaling on the device Optic  
Signaling contact Yes  
Connection cross section solid / stranded max. 1.5  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
System configuration  
With interference suppressor filter No  
Voltage protection level max. (by In) [Up] <0.9 kV  
Nominal discharge surge current (8/20) (L-N) 20  
Nominal cross section conductor 1.5 - 10.0 mm²
Total discharge current (8/20) (L N-PE) 60  
With remote signalling contact Yes  
Mounting method DIN rail (top hat rail) 35 mm  
Nominal discharge current [In] 5/Pol  
Category type 3 Yes  
Voltage protection level L-N [Up] 0.9  
Degree of protection (IP) IP20  
Construction size 2 modular spacing  
Standards
Homologation VDE, ÖVE und UL  
Test standards Germany  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 61643-11  
Commercial specification
Customs number 85363000  
country of origin NUL  
Logistic specification
VPE Weight 0.37