Categories

Junction box PV GAK 114 PG

Characteristics
Generator boxes with preassembled fuse holders, surge protection and grounding plate:

Legend
a) type 1+2 GAK + FUS 60 VGPVS-1000-4ST-1MPP
b) type 1+2 GAK + FUS 50 PVS-1000-4ST-1MPP
c) type 1+2 GAK + FUS 50 VGPVS-1000-4ST-1MPP
d) type 2 GAK + FUS 50 PV-1000-4ST-1MPP

Nominal line voltage Un DC
1000 V  
Follow current [IF]
0 kA  
Fault indication
mechanisch, Rot  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Integrated backup fuse
No  
Exhausting
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
degree of protection
IP65  
number of modules
20  
contract rail
DIN-Schiene  
String / MPP
4ST-1MPP  
inputs PG / MC4
PG  
outputs PG / MC4
PG  
Ground base plate
Yes  
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Nominal cross section conductor Response time [ta] Voltage protection level [Up] comment VPE Quantity
   
Junction box PVGAK+FUS60VG-1000-4ST-1MPP PG 296.154.266 969 112 514 T1 / T2 ≤1200VDC 12.5 40 6 - 35 ≤25 2.8 a) 1
Junction box PV GAK + FUS 50 PVS-1000-1ST-1MPP 296.154.866 969 112 574 T1 / T2 ≤1200VDC 6.25 40 2.5 - 25 ≤25 2.6 b) 1
Junction box PV GAK + 50VG-1000-1ST-1MPP 296.154.466 969 112 534 T1 / T2 ≤1200VDC 6.25 40 2.5 - 25 ≤25 2.8 c) 1
Junction box PVGAK+FUS50-1000-4ST-1MPP PG 296.154.666 969 112 554 T2 ≤1200VDC 5 40 2.5 - 25 ≤25 2.6 d) 1