Categories

Junction box PV GAK 111-MC4

Characteristics
Generator boxes with preassembled surge protection and grounding plate:

Legend
a) type 1+2 GAK + DIS 60 VGPVS-1000-2ST-1MPP
b) type 1+2 GAK + DIS 50 PVS-1000-2ST-1MPP
c) type 1+2 GAK + DIS 50 VGPVS-1000-2ST-1MPP
d) type 2 GAK + DIS 50 PV-1000-2ST-1MPP

Nominal line voltage Un DC
1000 V  
Follow current [IF]
0 kA  
Fault indication
mechanisch, Rot  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Integrated backup fuse
No  
Exhausting
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
degree of protection
IP65  
number of modules
8  
contract rail
DIN-Schiene  
String / MPP
2ST-1MPP  
inputs PG / MC4
MC 4  
outputs PG / MC4
MC 4  
Ground base plate
Yes  
Switching capacity voltage max. Uoc Max.
1000 V  
Switching current max. Isc. Max.
30 A  
Cross-sectional area
6 mm²  
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor comment VPE Quantity
   
Junction box PVGAK+DIS60VG-1000-2ST-1MPP MC4 296.050.351 969 112 094 T1 / T2 ≤1200VDC 12.5 40 ≤25 2.8 6 - 35 a) 1
Junction box PV GAK+DIS 50 PVS-1000-2ST-1MPP 296.050.951 969 112 204 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.6 2.5 - 25 b) 1
Junction box PV GAK+DIS50VG-1000-2ST-1MPP 296.050.551 969 111 864 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.8 2.5 - 25 c) 1
Junction box PVGAK+DIS50-1000-2ST-1MPP MC4 296.050.751 969 111 974 T2 ≤1200VDC 5 40 ≤25 2.6 2.5 - 25 d) 1