Photovoltaics surge protection T1+T2 DS 50 VGPVS
Characteristics
- Surge protector photovoltaic type 1+2
- 10 years warranty
- Iimp = 5kA/pole (10/350
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling
Discharge current max. (8/20) µs [Imax]
60 kA
Operating current [Ic]
0 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
Unendlich
Fault indication
Mechanisch, Rot
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
Energetically coordinated protective effect to the terminal
Yes
Exhausting
No
Nominal voltage DC
1000 V
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
3 modular spacing
System configuration DC
Yes
Integrated backup fuse
No
Degree of protection (IP)
IP20
Homologation
VDE, ÖVE und UL
Test standards USA
UL 1449 ed.3
Test standards Europe
EN 50539-11
Test standards France
UTE C61-740-51