Categories

291.130.242 DAC50VGS-11-275, Type 2+3 291.130.242

New

Type: DAC50VGS

Characteristics
- surge protector type 2+3
- 10 years warranty
{- Ableitfähigkeit pro Pol: In = 20kA; Imax = 50kA}
- 10 years warranty
{- Steckbares Schutzmodul}
{- Erzeugt keinen (Netz-) Folgestrom, Betriebs- und Leckstromfrei}
- remote signaling

Article No. 291.130.242
E-Number 808 488 340
Technical specification
SPD type T2 / T3  
Network configuration Yes  
Number of poles 1+1  
Continuous voltage AC max. 275 V  
Nominal line voltage Un AC 230 V  
Nominal frequency [fn] 0 - 100 Hz  
TOV-voltage L-N [UT] 335 V / 5 sec.  
Operating current [Ic] 0 kA  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] unendlich kA eff  
Nominal discharge surge current (8/20) 20 kA  
Discharge current max. (8/20) µs [Imax] 50 kA  
max. discharge current (Imax) 50 kA  
Combined shock [Uoc] 6 kV  
Voltage protection level max. (by In) [Up] 1.5 kV  
Protection level max. (at Imax) 1.5 kV  
Voltage protection level [Up] 1.5 kV  
Response time [ta] <20 ns  
Exhausting No  
Short circuit resistance (Icw) 50 kA  
Integrated backup fuse No  
Fuse max. (gG) 160 A  
Signaling on the device Optic  
Nominal cross section conductor 2.5 - 25 mm²
Remote signalling Yes  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V/0,5 A (AC) / 30 V / 3 A (DC)  
Fault indication mechanisch, Rot  
Mounting on Hutschiene 35mm  
Temperature range -40 - 85 °C
Construction size 2 modular spacing  
Mounting method DIN rail (top hat rail) 35 mm  
Degree of protection IP 20  
Degree of protection (IP) IP20  
Standards
Test standards Germany DIN EN 61643-11  
Test standards Europe DIN EN 61643-11  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.4  
Test standards France DIN EN 61643-11  
Homologation KEMA / EAC  
Commercial specification
Customs number 85363000  
country of origin RC