Categories
Article No. 296.050.803
E-Number 969 112 134
Technical specification
SPD type T1 / T2  
Number of poles 2  
max. discharge current (Imax) 40 kA  
Nominal line voltage Un DC 1000 V  
Impulse current [Iimp]_(10/350) 6.25 kA  
Nominal discharge surge current (8/20) 15 kA  
Voltage protection level [Up] 2.6 kV  
Operation voltage max. [Uc] ≤1200VDC  
Follow current [IF] 0 kA  
Response time [ta] ≤25 ns  
Short circuit resistance (Icw) 1 kA  
Fault indication mechanisch, Rot  
Total discharge current (8/20) (L N-PE) 60 kA  
Temperature range -40 - 85 °C
Signaling on the device Optic  
Signaling contact Yes  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V/0,5 A (AC) / - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal Yes  
System configuration DC Yes  
Construction size 3 modular spacing  
Nominal discharge current [In] 15/Pol  
Nominal cross section conductor 2.5 - 25 mm²
Integrated backup fuse No  
Exhausting No  
Mounting method DIN rail (top hat rail) 35 mm  
Degree of protection (IP) IP20  
Casing
degree of protection IP65  
number of modules 20  
contract rail DIN-Schiene  
String / MPP 3ST-3MPP  
inputs PG / MC4 MC 4  
outputs PG / MC4 MC 4  
Standards
Test standards USA UL 1449 ed.3  
Test standards Europe EN 50539-11  
Test standards France UTE C61-740-51  
comment b)  
Commercial specification
Customs number 85372000  
country of origin CH  
Texte
comment b)  
Logistic specification
VPE Weight 3.92 kg