Categories

Junction box PV GAK 212-MC4

Characteristics
Generator boxes with preassembled surge protection and grounding plate:

Legend
a) type 1+2 GAK + DIS 60 VGPVS-1000-4ST-2MPP
b) type 1+2 GAK + DIS 50 PVS-1000-4ST-2MPP
c) type 1+2 GAK + DIS 50 VGPVS-1000-4ST-2MPP
d) type 2 GAK + DIS 50 PV-1000-4ST-2MPP

Nominal line voltage Un DC
1000 V  
Follow current [IF]
0 kA  
Fault indication
mechanisch, Rot  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Integrated backup fuse
No  
Exhausting
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
degree of protection
IP65  
number of modules
20  
contract rail
DIN-Schiene  
String / MPP
4ST-2MPP  
inputs PG / MC4
MC 4  
outputs PG / MC4
MC 4  
Ground base plate
Yes  
Switching capacity voltage max. Uoc Max.
1000 V  
Switching current max. Isc. Max.
30 A  
Cross-sectional area
6 mm²  
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor comment VPE Quantity
   
Junction box PVGAK+DIS60VG-1000-4ST-2MPP MC4 296.050.352 969 112 104 T1 / T2 ≤1200VDC 12.5 40 ≤25 2.8 6 - 35 a) 1
Junction box PV GAK+DIS 50 PVS-1000-4ST-2MPP 296.050.952 969 112 214 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.6 2.5 - 25 b) 1
Junction box PV GAK+DIS50VG-1000-4ST-2MPP 296.050.552 969 111 874 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.8 2.5 - 25 c) 1
Junction box PVGAK+DIS50-1000-4ST-2MPP MC4 296.050.752 969 111 984 T2 ≤1200VDC 5 40 ≤25 2.6 2.5 - 25 d) 1